From the maker · the maker’s description

The Square D Homeline 200 Amp 40-Space 80-Circuit Indoor Convertible Main Breaker Qwik-Grip Load Center with cover for Plug-on Neutral breakers is UL listed for residential and commercial power distribution. This load center is built with a plated, aluminum bus bar that is tested and listed only for Homeline circuit breakers. Homeline load centers are designed for the value-minded contractors, remodelers, builders and homeowners. Homeline load centers are engineered for fast installation and wire savings.

  • California residents
  • Innovative cable entry system quickly grips the branch wires while eliminating steel KO's and cable connectors for a faster installation
  • Includes a fully distributed neutral bar, allowing for the installation of Homeline plug-on neutral combination arc fault breakers on any space
  • Each pole space accepts full-size, tandem or quad breakers
  • Ground and neutral bars accept up to (3) #10-14 equipment grounds
  • Includes a combination flush/surface indoor cover)
  • Accommodates plug-on secondary surge arrestor (sold separately)
  • Overhead/underground feed simply by rotating the device before installing
  • Single phase
  • Rated 120/240 VAC and 22,000 air short circuit current rating
  • Automatic flush adjusting cover requires less time to complete the job
  • Designed with straight-in mains to save expensive cable and time
  • Distributed split branch neutral with terminal screws backed out offering with up to 50% more terminals than UL requires increases wiring flexibility saving installation time and simplifies wiring
  • Thermoplastic interior assembly is among the most rugged in the industry
  • Slot/square drive screws let you use either standard flat blade screwdriver or square-head driver for positive drive and proper torque
  • Protection from damage or theft on the job site, interiors can be easily removed with a single captive screw
  • 3 ground bar mounting locations (left, right and end) let you pick the easiest spot to wire
  • Made in the USA
SKU
1182212293
Spaces
40
Mounting
Plug-On Neutral
Location
Indoor
Circuits
80
Item Weight
38
Load Center Mounting Type
Flush, Surface
Voltage (volts)
120/240
Load Center Type
Main Breaker
Electrical Product Type
Load Center
Indoor/Outdoor
Indoor
Product Weight (lb.)
38
Phase Type
1 Phase
Maximum Amperage (amps)
200
Load center width (in.)
14.25
Load center depth (in.)
3.75
Load center height (in.)
39.37
Certifications and Listings
UL Listed

Specifications are provided by the manufacturer. Brand names are trademarks of their owners.

Guide

Before you buy a breaker

  1. 1

    Match the panel

    Find the brand and series on the label inside the panel door. Homeline and QO are both Square D, and they do not interchange.

  2. 2

    Match the wire

    The breaker protects the wire. For copper: 14 AWG on 15 A, 12 AWG on 20 A, 10 AWG on 30 A.

  3. 3

    Protection

    Standard, AFCI (arc fault), GFCI (ground fault) or dual function. Your local code says which circuits need which.

  4. 4

    Tandem and quad

    Two circuits in one space, only in the slots the panel label allows.