Electrical

Details & specifications.

From the maker · the maker’s description

The GE 15 Amp Single Pole Ground Fault Circuit Breaker with Self-Test features a tin plated copper stab that ensures a durable, long-lasting, and corrosion-resistant connection. It serves as a replacement for GFCI wall outlets and provides a reliable means to locate the source of a tripped circuit (back to the electrical panel). No more guessing which outlet to reset. The Self-Test function is a UL requirement for all GFCI devices, starting in June 2015. This GFCI variant ensures proper performance by conducting periodic diagnostic tests on its ground circuitry. In case of any issues, the breaker will trip and require replacement. The unit provides protection against overloads, short circuits, and ground faults, quickly shutting off power to prevent serious shock. It also detects even the lowest levels of electrical current leakage (ground faults). With a Class A 5mA ground fault circuit interrupter, it is suitable for wire range #14-8 AWG CU/#12-8.

Amps
15 A
Poles
1-pole
Protection
GFCI
Type
Single Pole
Mounting
Plug-On
Item Weight
.479
Voltage (volts)
120
Product Weight (lb.)
.479
Pack Size
1
Power Distribution Features
No Additional Features
Interruption Type
GFCI
Electrical Product Type
Breaker
Product Depth (in.)
3
Product Height (in.)
4.5
Product Width (in.)
1.25
Certifications and Listings
UL Listed
Manufacturer Warranty
One year warranty from first use

Specifications are provided by the manufacturer. Brand names are trademarks of their owners.

Guide

Before you buy a breaker

  1. 1

    Match the panel

    Find the brand and series on the label inside the panel door. Homeline and QO are both Square D, and they do not interchange.

  2. 2

    Match the wire

    The breaker protects the wire. For copper: 14 AWG on 15 A, 12 AWG on 20 A, 10 AWG on 30 A.

  3. 3

    Protection

    Standard, AFCI (arc fault), GFCI (ground fault) or dual function. Your local code says which circuits need which.

  4. 4

    Tandem and quad

    Two circuits in one space, only in the slots the panel label allows.